WFD-T T-TAP TYPE WATER FLOW DETECTOR WITH RETARD

Fig No.: WFD-T

FEATURES & SPECIFICATIONS

  • Conforms to FM1042-2016 & UL346
  • Two conduit opening of ½”. One open; one knock-out type
  • Sensitivity range : 4 … 10 usgpm
  • Contact rating : Two sets of SPDT (Form C) 10Amps (125/250 VAC) / 2Amps (24VDC)
  • Enclosure rating : NEMA 4 – suitable for indoor / outdoor
  • Compatible pipe : Steel pipe, Schedule 10 through 40
  • Special tamper screws to prevent disassembly
  • Maximum surge : 5.5 m/s
  • Time delay adjustment via rotating dial
  • Two sets Micro-switch, 100% synchronization
  • Working pressure : Max. 31bar / 450psi
  • Working temperature : 4.5°C … 49°C
  • Available in aluminium or ABS casing

FM Approved.

Ordering Model and Dimensions

Model Description Pipe Size W H D
WFD-T-025 T-Tap Type Water Flow Detector 25mm (1″) 95.25mm 168.65mm 54mm
WFD-T-032 T-Tap Type Water Flow Detector 32mm (1¼”) 95.25mm 177.3mm 62.5mm
WFD-T-040 T-Tap Type Water Flow Detector 40mm (1½”) 95.25mm 183.65mm 69mm
WFD-T-050 T-Tap Type Water Flow Detector 50mm (2″) 95.25mm 196.85mm 82mm